Solid-wall pressure pipe for potable water mains, transmission lines and building service. Blue identification stripe, coil or straight length, butt-fusion and electrofusion jointing.




Dial in the pressure class first, then the diameter. If you are unsure, send the working pressure and we will recommend the SDR.
Each cell gives wall thickness e (mm) above and mass per metre (kg/m) below.
| OD (mm) | Wall thickness e (mm) / weight (kg/m) | ||||||
|---|---|---|---|---|---|---|---|
| SDR 41PN4 | SDR 26PN6 | SDR 17PN10 | SDR 13.6PN12.5 | SDR 11PN16 | SDR 9PN20 | SDR 7.4PN25 | |
| 20 | 0.50.03 | 0.80.05 | 1.20.07 | 1.50.08 | 1.80.1 | 2.20.12 | 2.70.14 |
| 25 | 0.60.04 | 1.00.07 | 1.50.11 | 1.80.13 | 2.30.16 | 2.80.19 | 3.40.22 |
| 32 | 0.80.07 | 1.20.11 | 1.90.17 | 2.40.21 | 2.90.25 | 3.60.31 | 4.30.36 |
| 40 | 1.00.12 | 1.50.17 | 2.40.27 | 2.90.32 | 3.60.39 | 4.40.47 | 5.40.56 |
| 50 | 1.20.18 | 1.90.27 | 2.90.41 | 3.70.51 | 4.50.61 | 5.60.75 | 6.80.88 |
| 63 | 1.50.28 | 2.40.44 | 3.70.66 | 4.60.81 | 5.70.98 | 7.01.18 | 8.51.39 |
| 75 | 1.80.4 | 2.90.63 | 4.40.93 | 5.51.15 | 6.81.39 | 8.31.66 | 10.11.97 |
| 90 | 2.20.58 | 3.50.91 | 5.31.35 | 6.61.65 | 8.22.01 | 10.02.4 | 12.22.85 |
| 110 | 2.70.87 | 4.21.33 | 6.52.02 | 8.12.48 | 10.03.0 | 12.23.58 | 14.94.25 |
| 125 | 3.01.1 | 4.81.73 | 7.42.61 | 9.23.2 | 11.43.89 | 13.94.63 | 16.95.48 |
| 140 | 3.41.39 | 5.42.18 | 8.23.24 | 10.34.01 | 12.74.85 | 15.65.82 | 18.96.87 |
| 160 | 3.91.83 | 6.22.86 | 9.44.25 | 11.85.25 | 14.56.33 | 17.87.59 | 21.68.97 |
| 180 | 4.42.32 | 6.93.58 | 10.65.39 | 13.26.61 | 16.48.05 | 20.09.6 | 24.311.35 |
| 200 | 4.92.87 | 7.74.44 | 11.86.66 | 14.78.17 | 18.29.93 | 22.211.84 | 27.014.01 |
| 225 | 5.53.62 | 8.75.65 | 13.28.39 | 16.510.32 | 20.512.58 | 25.015.0 | 30.417.75 |
| 250 | 6.14.46 | 9.66.92 | 14.710.38 | 18.412.79 | 22.715.48 | 27.818.53 | 33.821.92 |
| 280 | 6.85.57 | 10.88.72 | 16.513.04 | 20.616.03 | 25.519.47 | 31.123.22 | 37.827.47 |
| 315 | 7.77.1 | 12.111.0 | 18.516.46 | 23.220.31 | 28.624.57 | 35.029.4 | 42.634.82 |
| 355 | 8.79.04 | 13.714.03 | 20.920.95 | 26.125.75 | 32.331.27 | 39.437.31 | 48.044.21 |
| 400 | 9.811.47 | 15.417.77 | 23.526.55 | 29.432.69 | 36.439.71 | 44.447.37 | 54.156.14 |
| 450 | 11.014.49 | 17.322.46 | 26.533.67 | 33.141.4 | 40.950.2 | 50.060.0 | 60.871.0 |
| 500 | 12.217.85 | 19.227.7 | 29.441.51 | 36.851.14 | 45.562.04 | 55.674.13 | 67.687.7 |
| 560 | 13.722.45 | 21.534.74 | 32.952.03 | 41.264.13 | 50.977.75 | 62.292.9 | 75.7109.99 |
| 630 | 15.428.4 | 24.243.98 | 37.165.99 | 46.381.08 | 57.398.45 | 70.0117.61 | 85.1139.12 |
e = OD ÷ SDR, mass at 955 kg/m³ (calculated). Confirm against the ISO 4427-2 / ISO 4437 thickness table before publishing; OD above 630 mm and SDR33/41 on request.
Resin batch and lot number on the mill certificate, food-contact grade, no recycled content.
Coil ≤ DN250 for long rural runs; 6 m / 12 m straight above that or where trench access is tight.
Specify SDR11 above 6 bar working pressure or where pump surge is expected.
Butt-fusion parameter sheet per diameter ships with every order.
For buried potable lines specify SDR17 (PN10) as a baseline; use SDR11 (PN16) above 6 bar or where surge is expected.
Attach a project list or drawing if you have one. If you are unsure about SDR, tell us the working pressure.
SDR is outside diameter divided by wall thickness — lower SDR means thicker wall. PN is nominal pressure in bar at 20 °C. PE100: SDR26 = PN6, SDR17 = PN10, SDR13.6 = PN12.5, SDR11 = PN16, SDR9 = PN20, SDR7.4 = PN25.
Coils suit DN250 and below and cut the number of joints on long runs. Straight 6 m or 12 m above DN250, or where access is tight.
Yes — several diameters plus fittings and valves in one 40HQ with a packing list per item.
[To confirm — put the real figure here.]